Are you in search of a reputable online distributor that can reliably source and ship top-notch military and defense parts, NSN parts, and aerospace parts? If so, we have you covered on Buy Mil-NSN Parts with our unrivaled inventory of offerings. Thank you for taking an interest in part number AM33MG6-30-250-4-60, a Eaton Corporation item that is listed alongside the description “Circuit Breaker” and the NSN 5925009336041. If you would like to learn more about this particular listing, you can always take the initial step of the procurement process via the submission of the quote request form on this page.
Note : We Will Not Share Your Information To Any Third Parties.
We organize our offerings in a variety of ways to make the search process simple for part number AM33MG6-30-250-4-60 and other similar items. For instance, this Eaton Corporation product is listed alongside the NSN 5925-00-933-6041, and it falls under Federal Supply Class (FSC) 5925 Circuit Breakers. Furthermore, through our rigorous vetting processes, careful part inspections, document verification practices, and more, we have established ourselves as a trusted distributor operating with AS9120B, ISO 9001:2015, and FAA AC 00-56B accreditation. With all of this in mind, begin the procurement process for part number AM33MG6-30-250-4-60 from CAGE Code 74193 on our website, and see why so many customers steadily depend on Buy Mil-NSN Parts for the NSN products they require.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-933-6041 Item Description: CIRCUIT BREAKER | 5925 | 009336041 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
AM33MG6-30-250-4-60 | E | 1 | C | A |
MRC | Criteria | Characteristic |
---|---|---|
CQXF | Inclosure Protection Type For Which Designed | EXPLOSION RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANT |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
BBRG | Storage Type | GENERAL PURPOSE WAREHOUSE |
CPLM | Maximum Continuous Load Current Rating Per Pole | 30.0 AMPERES AC ALL LOCATIONS |
AKPX | Pole Quantity | 2 |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 AC ALL LOCATIONS |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
AFJN | Fragility Factor | MODERATELY RUGGED |
CPRJ | Trip Release Method | MAGNETIC-HYDRAULIC ALL LOCATIONS |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
AJEC | Boss Height | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 150.0 ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
AEHA | Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
ADAT | Body Width | 1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM |
TTQY | Terminal Type And Quantity | 4 THREADED STUD |
THSD | Thread Series Designator | UNC |
CPRX | Actuator Position Designation | AT EACH POLE |
CPRT | Manual Actuator Type And Quantity | 2 TOGGLE |
CPSM | Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
CPRW | Actuator Function | TRIP-RESET |
CQJX | Nominal Thread Size | 0.138 INCHES |
AXHR | Mounting Facility Type And Quantity | 4 THREADED HOLE |
ADTV | Case Material | PLASTIC |
AJWX | Mounting Surface To Terminal End Distance | 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM |
ADAQ | Body Length | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
AAQL | Body Style | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
APNQ | Arc Quenching Method | AIR |
CMLP | Thread Quantity Per Inch | 32 |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 1000.0 AC ALL LOCATIONS |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 4.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 11.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRQ | Reset Method | MANUAL |
MRC | Decoded Requirement | Clear Text Reply |
CPRY | External Actuator Linkage Arrangement | ONE AND TWO LINKED |