MRC | Criteria | Characteristic |
---|
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.060 INCHES NOMINAL |
AKPX | POLE QUANTITY | 4 |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SECOND LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3500.0 AC FIRST LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3500.0 AC SECOND LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCKPROOF AND VIBRATIONPROOF AND MOISTURE RESISTANT AND CORROSION RESISTANT |
CWJK | CASE MATERIAL | PLASTIC |
AJEC | BOSS HEIGHT | 0.150 INCHES NOMINAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC AND 50.0 AMPERES DC FOURTH LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC AND 50.0 AMPERES DC THIRD LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC AND 65.0 DC THIRD LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC FIRST LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
THSD | THREAD SERIES DESIGNATOR | UNC |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC FIRST LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC SECOND LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC AND 65.0 DC FOURTH LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3500.0 AC AND 2000.0 DC THIRD LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE,TWO,THREE,AND FOUR LINKED |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 22.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 8 THREADED STUD |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 3.030 INCHES NOMINAL |
ADAT | BODY WIDTH | 3.015 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.321 INCHES MAXIMUM |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3500.0 AC AND 2000.0 DC FOURTH LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CTJS | UNPACKAGED UNIT WEIGHT | 14.800 OUNCES NOMINAL |