Item Name | Circuit Breaker |
Federal Supply Group (FSG) | Electrical and Electronic Equipment Components |
Federal Supply Class (FSC) | 5925 Circuit Breakers |
National Item Identification Number (NIIN) | 00-681-1044 (006811044) |
NCB Code | USA (00) |
Manufacturer | Eaton Corporation, General Electric Company, Mpb Corporation |
Part Number | Manufacturer | Item Name | Cage Code | RFQ |
---|---|---|---|---|
33635MG4-5-250VAC | eaton corporation | circuit breaker | 74193 | RFQ |
33635MG4-5-250VAC60C3 | eaton corporation | circuit breaker | 74193 | RFQ |
3363SMG4-5-250-60-3 | eaton corporation | circuit breaker | 74193 | RFQ |
7700590P15 | general electric company | circuit breaker | 01002 | RFQ |
7700590P15 | mpb corporation | circuit breaker | 33173 | RFQ |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 5.240 INCHES MINIMUM AND 5.260 INCHES MAXIMUM |
ADAT | BODY WIDTH | 2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM |
ADAU | BODY HEIGHT | 2.677 INCHES MINIMUM AND 2.697 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.349 INCHES MINIMUM AND 4.369 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.974 INCHES MINIMUM AND 0.994 INCHES MAXIMUM |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 3.052 INCHES MINIMUM AND 3.072 INCHES MAXIMUM |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.974 INCHES MINIMUM AND 0.994 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.208 INCHES MINIMUM AND 0.228 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 3 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE AND 4 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.164 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.320 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
Components Related to NSN - 5925-00-681-1044, 5925006811044 | ||||
5935-00-789-6206 (5935007896206) | 5999-00-195-5441 (5999001955441) | 5930-00-426-2671 (5930004262671) | 5935-01-210-1780 (5935012101780) | |
5990-01-114-9896 (5990011149896) | 5925-01-198-7912 (5925011987912) | 5995-01-152-5092 (5995011525092) | 5910-00-989-4896 (5910009894896) | |
5961-00-172-8326 (5961001728326) | 5950-00-971-5673 (5950009715673) | 5925-00-235-0046 (5925002350046) | 5962-01-421-9559 (5962014219559) | |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.
Request for Quote